Const
Readonly
attributes: { Readonly
maxThis attribute specifies the maximum compensated pressure the pump can achieve when it is working with the ControlMode attribute set to ProportionalPressure.
Valid range is –3,276.7 kPa to 3,276.7 kPa (steps of 0.1 kPa). Null if the value is invalid.
Readonly
maxThis attribute specifies the maximum flow the pump can achieve when it is working with the ControlMode attribute set to ConstantFlow.
Valid range is 0 m/h to 6,553.4 m/h (steps of 0.1 m/h). Null if the value is invalid.
Readonly
maxThis attribute specifies the maximum pressure the pump can achieve when it is working with the ControlMode attribute set to ConstantPressure.
Valid range is –3,276.7 kPa to 3,276.7 kPa (steps of 0.1 kPa). Null if the value is invalid.
Readonly
maxThis attribute specifies the maximum speed the pump can achieve when it is working with the ControlMode attribute set to ConstantSpeed.
Valid range is 0 to 65,534 RPM (steps of 1 RPM). Null if the value is invalid.
Readonly
maxThis attribute specifies the maximum temperature the pump can maintain in the system when it is working with the ControlMode attribute set to ConstantTemperature.
MaxConstTemp shall be greater than or equal to MinConstTemp
Valid range is –273.15 °C to 327.67 °C (steps of 0.01 °C). Null if the value is invalid.
Readonly
minThis attribute specifies the minimum compensated pressure the pump can achieve when it is working with the ControlMode attribute set to ProportionalPressure.
Valid range is –3,276.7 kPa to 3,276.7 kPa (steps of 0.1 kPa). Null if the value is invalid.
Readonly
minThis attribute specifies the minimum flow the pump can achieve when it is working with the Con
trolMode attribute set to ConstantFlow.
Valid range is 0 m/h to 6,553.4 m/h (steps of 0.1 m/h). Null if the value is invalid.
Readonly
minThis attribute specifies the minimum pressure the pump can achieve when it is working with the ControlMode attribute set to ConstantPressure.
Valid range is –3,276.7 kPa to 3,276.7 kPa (steps of 0.1 kPa). Null if the value is invalid.
Readonly
minThis attribute specifies the minimum speed the pump can achieve when it is working with the ControlMode attribute set to ConstantSpeed.
Valid range is 0 to 65,534 RPM (steps of 1 RPM). Null if the value is invalid.
Readonly
minThis attribute specifies the minimum temperature the pump can maintain in the system when it is working with the ControlMode attribute set to ConstantTemperature.
Valid range is –273.15 °C to 327.67 °C (steps of 0.01 °C). Null if the value is invalid.